XT 300

10 - 80 kVA

XT 300 is, True online, Double conversion UPS Systems, manufactured with the state of the art, PWM and IGBT technology, producing microprocessor controlled pure sinewave output to critical loads.

Show More

Areas of Usage

General Features

XT 300

XT 300

10 - 80 kVA

XT 300 is, True online, Double conversion UPS Systems, manufactured with the state of the art, PWM and IGBT technology, producing microprocessor controlled pure sinewave output to critical loads.

  • Output isolation transformer
  • Up to 92% efficiency
  • Static by-pass
  • LCD front panel
  • 128 events alarm memory (4000 alarms)
  • RS232 and relay contacts
  • Custom input and output voltage ranges
  • SNMP compatible communication
  • T-MON remote monitoring soſtware
  • Parallel operation up to 4 devices
  • High performance at nonlinear loads
  • Custom input voltage and frequency ranges
  • Manufactured according to EC Directive; EN62040
  • 2 years warrany
TECHNICIAL SPECIFICATIONS
Nominal power (kVA)10
INPUT
Voltage220/380 (230/400 VAC) 3P + N + G ± 15%
By-Pass Voltage220/380 (230/400 VAC) 3P + N ± 10%
Frequency50Hz (60Hz on request) ± 5%
OUTPUT
Power (kW)8
Power factor0,8
Voltage380/400 VAC 3P + N
GVoltage toleranceStatic: ± 1%, Dynamic: ± 5%
Frequency50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2%, free running: ± 0.2%
Efficiency (at 100% load)89-91%
Output current crest factor3:1
Overload100%-125% load: 10 min., 125%-150% load: 1 min., >150% load: by pass
Short circuit protectionElectronic short circuit protection
THDLinear load: < 3%, Non linear load: < 5%
BATTERIES
TypeSealed Lead Acid - Maintenance Free
Number30
Float charging voltage405 VDC
Float / End of dischg voltage300 VDC
Operating temperature25ºC
Battery protectionAutomatic circuit breaker
Automatic TestingAutomatic/Manuel
GENEL
StandardsEN 62040-1, EN 62040-2
Serial communicationDry contacts & RS232
SoſtwareT-Mon UPS Management Software
Operating temperature0ºC - 40ºC
CoolingForced air cooling
Relative humidity< 90% (non-condensing)
Protection classIP20
Altitude< 2000m
Noise level< 56 dBA
Weight (kg)220
Dimension (mm) HxWxD505x655x1150
OPTIONS
Input / Output voltagePlease ask
Input transformerGalvanic isolation transformer at the input (in external cabinet)
Input THDI10% (with 12 pulse or 18 pulse rectifier, according to UPS range), %5 (with 18 pulse rectifier, + filter), up to 100kVA
Input Voltage regulation0.95 - 0.98 (with 18 pulse rectifier)
Parralel OperationN+1 (up to 4 units) In 18Pulse applications, the standard chassis dimensions may change.
CommunicationSNMP, MODBUS, Remote Mon. Panel, RS485
Battery temperature compensationOptional
TECHNICIAL SPECIFICATIONS
Nominal power (kVA)15
INPUT
Voltage220/380 (230/400 VAC) 3P + N + G ± 15%
By-Pass Voltage220/380 (230/400 VAC) 3P + N ± 10%
Frequency50Hz (60Hz on request) ± 5%
OUTPUT
Power (kW)12
Power factor0,8
Voltage380/400 VAC 3P + N
GVoltage toleranceStatic: ± 1%, Dynamic: ± 5%
Frequency50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2%, free running: ± 0.2%
Efficiency (at 100% load)89-91%
Output current crest factor3:1
Overload100%-125% load: 10 min., 125%-150% load: 1 min., >150% load: by pass
Short circuit protectionElectronic short circuit protection
THDLinear load: < 3%, Non linear load: < 5%
BATTERIES
TypeSealed Lead Acid - Maintenance Free
Number30
Float charging voltage405 VDC
Float / End of dischg voltage300 VDC
Operating temperature25ºC
Battery protectionAutomatic circuit breaker
Automatic TestingAutomatic/Manuel
GENEL
StandardsEN 62040-1, EN 62040-2
Serial communicationDry contacts & RS232
SoſtwareT-Mon UPS Management Software
Operating temperature0ºC - 40ºC
CoolingForced air cooling
Relative humidity< 90% (non-condensing)
Protection classIP20
Altitude< 2000m
Noise level< 56 dBA
Weight (kg)260
Dimension (mm) HxWxD505x655x1150
OPTIONS
Input / Output voltagePlease ask
Input transformerGalvanic isolation transformer at the input (in external cabinet)
Input THDI10% (with 12 pulse or 18 pulse rectifier, according to UPS range), %5 (with 18 pulse rectifier, + filter), up to 100kVA
Input Voltage regulation0.95 - 0.98 (with 18 pulse rectifier)
Parralel OperationN+1 (up to 4 units) In 18Pulse applications, the standard chassis dimensions may change.
CommunicationSNMP, MODBUS, Remote Mon. Panel, RS485
Battery temperature compensationOptional
TECHNICIAL SPECIFICATIONS
Nominal power (kVA)20
INPUT
Voltage220/380 (230/400 VAC) 3P + N + G ± 15%
By-Pass Voltage220/380 (230/400 VAC) 3P + N ± 10%
Frequency50Hz (60Hz on request) ± 5%
OUTPUT
Power (kW)16
Power factor0,8
Voltage380/400 VAC 3P + N
GVoltage toleranceStatic: ± 1%, Dynamic: ± 5%
Frequency50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2%, free running: ± 0.2%
Efficiency (at 100% load)89-91%
Output current crest factor3:1
Overload100%-125% load: 10 min., 125%-150% load: 1 min., >150% load: by pass
Short circuit protectionElectronic short circuit protection
THDLinear load: < 3%, Non linear load: < 5%
BATTERIES
TypeSealed Lead Acid - Maintenance Free
Number30
Float charging voltage405 VDC
Float / End of dischg voltage300 VDC
Operating temperature25ºC
Battery protectionAutomatic circuit breaker
Automatic TestingAutomatic/Manuel
GENEL
StandardsEN 62040-1, EN 62040-2
Serial communicationDry contacts & RS232
SoſtwareT-Mon UPS Management Software
Operating temperature0ºC - 40ºC
CoolingForced air cooling
Relative humidity< 90% (non-condensing)
Protection classIP20
Altitude< 2000m
Noise level< 56 dBA
Weight (kg)284
Dimension (mm) HxWxD505x655x1150
OPTIONS
Input / Output voltagePlease ask
Input transformerGalvanic isolation transformer at the input (in external cabinet)
Input THDI10% (with 12 pulse or 18 pulse rectifier, according to UPS range), %5 (with 18 pulse rectifier, + filter), up to 100kVA
Input Voltage regulation0.95 - 0.98 (with 18 pulse rectifier)
Parralel OperationN+1 (up to 4 units) In 18Pulse applications, the standard chassis dimensions may change.
CommunicationSNMP, MODBUS, Remote Mon. Panel, RS485
Battery temperature compensationOptional
TECHNICIAL SPECIFICATIONS
Nominal power (kVA)30
INPUT
Voltage220/380 (230/400 VAC) 3P + N + G ± 15%
By-Pass Voltage220/380 (230/400 VAC) 3P + N ± 10%
Frequency50Hz (60Hz on request) ± 5%
OUTPUT
Power (kW)24
Power factor0,8
Voltage380/400 VAC 3P + N
GVoltage toleranceStatic: ± 1%, Dynamic: ± 5%
Frequency50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2%, free running: ± 0.2%
Efficiency (at 100% load)90-92%
Output current crest factor3:1
Overload100%-125% load: 10 min., 125%-150% load: 1 min., >150% load: by pass
Short circuit protectionElectronic short circuit protection
THDLinear load: < 3%, Non linear load: < 5%
BATTERIES
TypeSealed Lead Acid - Maintenance Free
Number30
Float charging voltage405 VDC
Float / End of dischg voltage300 VDC
Operating temperature25ºC
Battery protectionAutomatic circuit breaker
Automatic TestingAutomatic/Manuel
GENEL
StandardsEN 62040-1, EN 62040-2
Serial communicationDry contacts & RS232
SoſtwareT-Mon UPS Management Software
Operating temperature0ºC - 40ºC
CoolingForced air cooling
Relative humidity< 90% (non-condensing)
Protection classIP20
Altitude< 2000m
Noise level< 56 dBA
Weight (kg)305
Dimension (mm) HxWxD505x655x1150
OPTIONS
Input / Output voltagePlease ask
Input transformerGalvanic isolation transformer at the input (in external cabinet)
Input THDI10% (with 12 pulse or 18 pulse rectifier, according to UPS range), %5 (with 18 pulse rectifier, + filter), up to 100kVA
Input Voltage regulation0.95 - 0.98 (with 18 pulse rectifier)
Parralel OperationN+1 (up to 4 units) In 18Pulse applications, the standard chassis dimensions may change.
CommunicationSNMP, MODBUS, Remote Mon. Panel, RS485
Battery temperature compensationOptional
TECHNICIAL SPECIFICATIONS
Nominal power (kVA)40
INPUT
Voltage220/380 (230/400 VAC) 3P + N + G ± 15%
By-Pass Voltage220/380 (230/400 VAC) 3P + N ± 10%
Frequency50Hz (60Hz on request) ± 5%
OUTPUT
Power (kW)32
Power factor0,8
Voltage380/400 VAC 3P + N
GVoltage toleranceStatic: ± 1%, Dynamic: ± 5%
Frequency50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2%, free running: ± 0.2%
Efficiency (at 100% load)90-92%
Output current crest factor3:1
Overload100%-125% load: 10 min., 125%-150% load: 1 min., >150% load: by pass
Short circuit protectionElectronic short circuit protection
THDLinear load: < 3%, Non linear load: < 5%
BATTERIES
TypeSealed Lead Acid - Maintenance Free
Number30
Float charging voltage405 VDC
Float / End of dischg voltage300 VDC
Operating temperature25ºC
Battery protectionAutomatic circuit breaker
Automatic TestingAutomatic/Manuel
GENEL
StandardsEN 62040-1, EN 62040-2
Serial communicationDry contacts & RS232
SoſtwareT-Mon UPS Management Software
Operating temperature0ºC - 40ºC
CoolingForced air cooling
Relative humidity< 90% (non-condensing)
Protection classIP20
Altitude< 2000m
Noise level< 56 dBA
Weight (kg)404
Dimension (mm) HxWxD575x820x1390
OPTIONS
Input / Output voltagePlease ask
Input transformerGalvanic isolation transformer at the input (in external cabinet)
Input THDI10% (with 12 pulse or 18 pulse rectifier, according to UPS range), %5 (with 18 pulse rectifier, + filter), up to 100kVA
Input Voltage regulation0.95 - 0.98 (with 18 pulse rectifier)
Parralel OperationN+1 (up to 4 units) In 18Pulse applications, the standard chassis dimensions may change.
CommunicationSNMP, MODBUS, Remote Mon. Panel, RS485
Battery temperature compensationOptional
TECHNICIAL SPECIFICATIONS
Nominal power (kVA)60
INPUT
Voltage220/380 (230/400 VAC) 3P + N + G ± 15%
By-Pass Voltage220/380 (230/400 VAC) 3P + N ± 10%
Frequency50Hz (60Hz on request) ± 5%
OUTPUT
Power (kW)48
Power factor0,8
Voltage380/400 VAC 3P + N
GVoltage toleranceStatic: ± 1%, Dynamic: ± 5%
Frequency50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2%, free running: ± 0.2%
Efficiency (at 100% load)90-92%
Output current crest factor3:1
Overload100%-125% load: 10 min., 125%-150% load: 1 min., >150% load: by pass
Short circuit protectionElectronic short circuit protection
THDLinear load: < 3%, Non linear load: < 5%
BATTERIES
TypeSealed Lead Acid - Maintenance Free
Number30
Float charging voltage405 VDC
Float / End of dischg voltage300 VDC
Operating temperature25ºC
Battery protectionAutomatic circuit breaker
Automatic TestingAutomatic/Manuel
GENEL
StandardsEN 62040-1, EN 62040-2
Serial communicationDry contacts & RS232
SoſtwareT-Mon UPS Management Software
Operating temperature0ºC - 40ºC
CoolingForced air cooling
Relative humidity< 90% (non-condensing)
Protection classIP20
Altitude< 2000m
Noise level< 60 dBA
Weight (kg)496
Dimension (mm) HxWxD575x820x1390
OPTIONS
Input / Output voltagePlease ask
Input transformerGalvanic isolation transformer at the input (in external cabinet)
Input THDI10% (with 12 pulse or 18 pulse rectifier, according to UPS range), %5 (with 18 pulse rectifier, + filter), up to 100kVA
Input Voltage regulation0.95 - 0.98 (with 18 pulse rectifier)
Parralel OperationN+1 (up to 4 units) In 18Pulse applications, the standard chassis dimensions may change.
CommunicationSNMP, MODBUS, Remote Mon. Panel, RS485
Battery temperature compensationOptional
TECHNICIAL SPECIFICATIONS
Nominal power (kVA)80
INPUT
Voltage220/380 (230/400 VAC) 3P + N + G ± 15%
By-Pass Voltage220/380 (230/400 VAC) 3P + N ± 10%
Frequency50Hz (60Hz on request) ± 5%
OUTPUT
Power (kW)64
Power factor0,8
Voltage380/400 VAC 3P + N
GVoltage toleranceStatic: ± 1%, Dynamic: ± 5%
Frequency50Hz / 60Hz
Frequency Tolerance Line synchronized: ± 2%, free running: ± 0.2%
Efficiency (at 100% load)90-92%
Output current crest factor3:1
Overload100%-125% load: 10 min., 125%-150% load: 1 min., >150% load: by pass
Short circuit protectionElectronic short circuit protection
THDLinear load: < 3%, Non linear load: < 5%
BATTERIES
TypeSealed Lead Acid - Maintenance Free
Number30
Float charging voltage405 VDC
Float / End of dischg voltage300 VDC
Operating temperature25ºC
Battery protectionAutomatic circuit breaker
Automatic TestingOtomatik / Manuel
GENEL
StandardsEN 62040-1, EN 62040-2
Serial communicationDry contacts & RS232
SoſtwareT-Mon UPS Management Software
Operating temperature0ºC - 40ºC
CoolingForced air cooling
Relative humidity< 90% (non-condensing)
Protection classIP20
Altitude< 2000m
Noise level< 60 dBA
Weight (kg)580
Dimension (mm) HxWxD720x820x1450
OPTIONS
Input / Output voltagePlease ask
Input transformerGalvanic isolation transformer at the input (in external cabinet)
Input THDI10% (with 12 pulse or 18 pulse rectifier, according to UPS range), %5 (with 18 pulse rectifier, + filter), up to 100kVA
Input Voltage regulation0.95 - 0.98 (with 18 pulse rectifier)
Parralel OperationN+1 (up to 4 units) In 18Pulse applications, the standard chassis dimensions may change.
CommunicationSNMP, MODBUS, Remote Mon. Panel, RS485
Battery temperature compensationOptional