TEOS 100 XL

1 - 10 kVA

• True double-conversion • Microprocessor control optimizes reliability • Input power factor correction • Output power factor 0.8 • Wide input voltage • Converter mode available • ECO mode for energy saving (Only available for 1-3kVA models)

Show More

Areas of Usage

General Features

TEOS 100 XL
  • True double-conversion
  • Microprocessor control optimizes reliability
  • Input power factor correction
  • Output power factor 0.8
  • Wide input voltage
  • Converter mode available
  • ECO mode for energy saving (Only available for 1-3kVA models)
  • Generator compatible
  • Adjustable battery numbers only available for 6/10kVA models
  • Adjustable charging current via LCD or soſtware (1A~ 6A) only available for 6/10kVA models
  • Emergency power off (EPO) function is only available for 6/10kVA models
  • Comprehensive display allows easy monitoring and access to UPS status
TECHNICIAL SPECIFICATIONS
PhaseSingle phase with ground
Capacity1000VA / 800W
INPUT
Nominal Voltage100/110/115/120/127VAC or 200/208/220/230/240VAC
Input voltage range60-150 VAC or 120-300 VAC (Based on load at 50%) 90-140 VAC or 180-280 VAC (Based on load at 100%)
Frequency range40Hz ~ 70 Hz
Power factor≥ 0.99 @ Nominal Voltage (100% load)
OUTPUT
Power factor0,8
Voltage100/110/115/120/127VAC or 200/208/220/230/240VAC
GVoltage tolerance± %1
Frequency range47~ 53 Hz or 57 ~ 63 Hz
Frequency range (batt. mode)50 Hz or 60Hz ± %0.5
Output current crest factor3:1 (maks)
THD≤ 3% THD (linear load) ≤ 6% THD (non-linear load)
Transfer time | AC Mode -> Battery ModeZero
Transfer time | Inverter -> bypass4 ms
Waveform (batt. mode)Pure Sinewave
EFFICIENCY
AC Mode%88
Battery Mode%83
BATTERY
Battery typeDepending on the applications
Numbers2
Typical recharge time4 hour recover to 90% capacity
Charging current (max.)1A/2A/4A/6A (adjustable)
Float charging voltage27.4VDC ± %1 - 41.9VDC ± %1
INDICATORS
LCDLoad level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
ALARM
Battery ModeSounding every 4 seconds
Low BatterySounding every second
OverloadSounding twice every second
FaultContinously sounding
PHYSICAL
Dimension (mm) HxWxD145x282x220
Weight (kg)4.1
ENVIRONMENT
Relative humidity20-90% RH @ 0- 40°C (non-condensing
Noise level< 50dBA @ 1 meter
Managament
Smart RS-232/USBSupports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC
Optional SNMPPower management from SNMP manager and web browser
TECHNICIAL SPECIFICATIONS
PhaseSingle phase with ground
Capacity2000VA / 1600W
INPUT
Nominal Voltage100/110/115/120/127VAC or 200/208/220/230/240VAC
Input voltage range60-150 VAC or 120-300 VAC (Based on load at 50%) 90-140 VAC or 180-280 VAC (Based on load at 100%)
Frequency range40Hz ~ 70 Hz
Power factor≥ 0.99 @ Nominal Voltage (100% load)
OUTPUT
Power factor0,8
Voltage100/110/115/120/127VAC or 200/208/220/230/240VAC
GVoltage tolerance± %1
Frequency range47~ 53 Hz or 57 ~ 63 Hz
Frequency range (batt. mode)50 Hz or 60Hz ± %0.5
Output current crest factor3:1 (maks)
THD≤ 3% THD (linear load) ≤ 6% THD (non-linear load)
Transfer time | AC Mode -> Battery ModeZero
Transfer time | Inverter -> bypass4 ms
Waveform (batt. mode)Pure Sinewave
EFFICIENCY
AC Mode%89
Battery Mode%85
BATTERY
Battery typeDepending on the applications
Numbers4
Typical recharge time4 hour recover to 90% capacity
Charging current (max.)1A/2A/4A/6A (adjustable)
Float charging voltage54.7 VDC ± %1 - 82.1VDC ± %1 - 109.4 VDC ± %1
INDICATORS
LCDLoad level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
ALARM
Battery ModeSounding every 4 seconds
Low BatterySounding every second
OverloadSounding twice every second
FaultContinously sounding
PHYSICAL
Dimension (mm) HxWxD145x397x220
Weight (kg)6.8
ENVIRONMENT
Relative humidity20-90% RH @ 0- 40°C (non-condensing
Noise level< 50dBA @ 1 meter
Managament
Smart RS-232/USBSupports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC
Optional SNMPPower management from SNMP manager and web browser
TECHNICIAL SPECIFICATIONS
PhaseSingle phase with ground
Capacity3000VA / 2400W
INPUT
Nominal Voltage100/110/115/120/127VAC or 200/208/220/230/240VAC
Input voltage range60-150 VAC or 120-300 VAC (Based on load at 50%) 90-140 VAC or 180-280 VAC (Based on load at 100%)
Frequency range40Hz ~ 70 Hz
Power factor≥ 0.99 @ Nominal Voltage (100% load)
OUTPUT
Power factor0,8
Voltage100/110/115/120/127VAC or 200/208/220/230/240VAC
GVoltage tolerance± %1
Frequency range47~ 53 Hz or 57 ~ 63 Hz
Frequency range (batt. mode)50 Hz or 60Hz ± %0.5
Output current crest factor3:1 (maks)
THD≤ 3% THD (linear load) ≤ 6% THD (non-linear load)
Transfer time | AC Mode -> Battery ModeZero
Transfer time | Inverter -> bypass4 ms
Waveform (batt. mode)Pure Sinewave
EFFICIENCY
AC Mode%90
Battery Mode%88
BATTERY
Battery typeDepending on the applications
Numbers6
Typical recharge time4 hour recover to 90% capacity
Charging current (max.)1A/2A/4A/6A (adjustable)
Float charging voltage82.1 VDC ± %1 - 109.4 VDC ± %1
INDICATORS
LCDLoad level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
ALARM
Battery ModeSounding every 4 seconds
Low BatterySounding every second
OverloadSounding twice every second
FaultContinously sounding
PHYSICAL
Dimension (mm) HxWxD145x397x220
Weight (kg)7.4
ENVIRONMENT
Relative humidity20-90% RH @ 0- 40°C (non-condensing
Noise level< 50dBA @ 1 meter
Managament
Smart RS-232/USBSupports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC
Optional SNMPPower management from SNMP manager and web browser
TECHNICIAL SPECIFICATIONS
PhaseSingle phase with ground
Capacity6000VA / 5400W
INPUT
Nominal Voltage208/220/230/240VAC
Input voltage range110-300 VAC (Based on load at 50%) 176-300 VAC (Based on load at 100%)
Frequency range46~54 Hz or 56~64 Hz
Power factor≥ 0.99 @ Nominal Voltage (100% load)
OUTPUT
Power factor0,9
Voltage208/220/230/240VAC
GVoltage tolerance± %1
Frequency range46~54 Hz or 56~64 Hz
Frequency range (batt. mode)50 Hz or 60Hz ± %0.5
Output current crest factor3:1 (maks)
THD≤ 3% THD (linear load) ≤ 6% THD (non-linear load)
Transfer time | AC Mode -> Battery ModeZero
Transfer time | Inverter -> bypassZero
Waveform (batt. mode)Pure Sinewave
EFFICIENCY
AC Mode%92
Battery Mode%90
BATTERY
Battery typeDepending on the applications
Numbers16-20 (adjustable)
Typical recharge time9 hour recover to 90% capacity
Charging current (max.)1A/2A/4A/6A (adjustable, only for 6A 16 pcs batt. configuration)
Float charging voltage273 VDC ± 1% (according to 20 batt.-powered configuration)
INDICATORS
LCDLoad level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
ALARM
Battery ModeSounding every 4 seconds
Low BatterySounding every second
OverloadSounding twice every second
FaultContinously sounding
PHYSICAL
Dimension (mm) HxWxD190x369x318
Weight (kg)12
ENVIRONMENT
Relative humidity0-95% RH @ 0-40°C (non-condensing)
Noise level< 50dBA @ 1 meter
Managament
Smart RS-232/USBSupports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC
Optional SNMPPower management from SNMP manager and web browser
TECHNICIAL SPECIFICATIONS
PhaseSingle phase with ground
Capacity10000VA / 9000W
INPUT
Nominal Voltage208/220/230/240VAC
Input voltage range110-300 VAC (Based on load at 50%) 176-300 VAC (Based on load at 100%)
Frequency range46~54 Hz or 56~64 Hz
Power factor≥ 0.99 @ Nominal Voltage (100% load)
OUTPUT
Power factor0,9
Voltage208/220/230/240VAC
GVoltage tolerance± %1
Frequency range46~54 Hz or 56~64 Hz
Frequency range (batt. mode)50 Hz or 60Hz ± %0.5
Output current crest factor3:1 (maks)
THD≤ 3% THD (linear load) ≤ 6% THD (non-linear load)
Transfer time | AC Mode -> Battery ModeZero
Transfer time | Inverter -> bypassZero
Waveform (batt. mode)Pure Sinewave
EFFICIENCY
AC Mode%93
Battery Mode%91
BATTERY
Battery typeDepending on the applications
Numbers16-20 (adjustable)
Typical recharge time9 hour recover to 90% capacity
Charging current (max.)1A/2A/4A/6A (adjustable, only for 6A 16 pcs batt. configuration)
Float charging voltage273 VDC ± 1% (according to 20 batt.-powered configuration)
INDICATORS
LCDLoad level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
ALARM
Battery ModeSounding every 4 seconds
Low BatterySounding every second
OverloadSounding twice every second
FaultContinously sounding
PHYSICAL
Dimension (mm) HxWxD190x442x318
Weight (kg)16
ENVIRONMENT
Relative humidity0-95% RH @ 0-40°C (non-condensing)
Noise level< 50dBA @ 1 meter
Managament
Smart RS-232/USBSupports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC
Optional SNMPPower management from SNMP manager and web browser