DS POWER SH

10 - 20 kVA

The new Tescom DS Power SH UPS appears as a cost effective and smaller footprint UPS. Using the 3 level inverter topology and control system, this series UPS have the latest DSP technology to be programmed to suit a wide variety of electrical...

Show More

Areas of Usage

General Features

DS POWER SH

IGBT RECTIFIER

DSP CONTROL

The new Tescom DS Power SH UPS appears as a cost effective and smaller footprint UPS. Using the 3 level inverter topology and control system, this series UPS have the latest DSP technology to be programmed to suit a wide variety of electrical environments without impending its performance. Efficiency, reliability and functionality are enhanced to levels unattainable with the old analogue technology. This technology does not only create significant increase in MTBF, but the capability of DSP to accurately manipulate signals at very high speed permits all the UPS subsystems to be controlled with greatly increased precision.

  • Smaller footprint
  • 3 Level topology
  • Transformerless UPS topology
  • Low input current total harmonic distortion (THD)
  • High input power factor
  • High efficiency up to 94%
  • Cold start function
  • Static and maintenance by-pass switch
  • Output short circuit and overload protection
  • External REPO switch input
  • 192 events memory (192 events 14.400 alarms)
  • Clock and calender (battery supported)
  • Automatic battery test ,remaining battery time indicator
  • Temperature compensated charge system (optional)
  • 1 RS232 serial port and 3 dry contact outputs (+2 optional)
  • 3 DSP controlled modular structure
  • Optional SNMP and MODBUS adaptors
  • Fulldigital structure
  • Fewer electronic components
  • Output current limiting
  • Advanced diagnostics for the input
  • Selectable input/output voltage/frequency range
  • Output DC leakage protection
  • Separate DSP for PFC 3 level battery protection
  • Charge / discharge current indicator
  • Advanced remote control features
  • Manufactured under CE,ISO9001,ISO14001,TSE and GOST international standards
  • 2 years warranty
TECHNICIAL SPECIFICATIONS
Nominal power (kVA)10
INPUT
Voltage380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional)
Frequency50Hz / 60Hz, ± %10
Power factor (at100% load)≥ 0.99
THDI (at 100% load)≤ 4% (depends on mains input conditions)
By-Pass Voltage380/400 VAC 3 Phase + N, ± 10%
ProtectionFuses, Voltage & Frequency Tolerance
OUTPUT
Power (kW)9
Power factor0,9 (1 optional)
Voltage380/400 VAC 3P + N , ± 1% (415 VAC optional)
Frequency50Hz / 60Hz
Frequency ToleranceLine synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Efficiency (at 100% load)%94
Output current crest factor3:1
Overload Protection100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other ProtectionsAdvanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD< 2% (at 100% linear load)
BATTERIES
TypeVRLA AGM / GEL / NiCd
Battery Number2x30 (±30): 60 pieces
Float charging voltage± 405 VDC
Float / End of dischg voltage± 300 VDC
Battery HousingExternal
Battery ambient temp25°C
Protections
Battery ambient temp3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic TestingStandard every 72 hours (adjustable)
GENEL
StandardsEN62040-1, EN62040-2, EN62040-3
User Interface4 satır LCD panel, Mimik led panel, 5 vektör butonlar, buzer
IndicatorsP-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
AdvancedSelf diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
CommunicationRS232 serial port, 4 standard DRY contact alarm relays
InputsEPO input
Genset KitStandard (programmable)
SoſtwareStandard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm LoggingStandard:with time & date 512 events
ProtectionsPower module over-temperature, Overcurrent, Temperature high alarm
Temperature Range0°C - 40°C
Protection classIP20
Relative humidity90% max. (non-condensing)
Altitude< 1000m above sea level
Noise level< 55 dBA
Weight (kg)47.5
Dimension (mm) HxWxD700x300x770 (without batt.) / 1000x300x800 (with 5ah batt.) /1170x300x800 (with 7-9ah batt.)
OPTIONS
Input / Output voltagePlease ask
Comm. adaptorsSNMP, MODBUS, RS485, Remote panel
SoſtwareT-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
TECHNICIAL SPECIFICATIONS
Nominal power (kVA)15
INPUT
Voltage380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional)
Frequency50Hz / 60Hz, ± %10
Power factor (at100% load)≥ 0.99
THDI (at 100% load)≤ 4% (depends on mains input conditions)
By-Pass Voltage380/400 VAC 3 Phase + N, ± 10%
ProtectionFuses, Voltage & Frequency Tolerance
OUTPUT
Power (kW)13,5
Power factor0,9 (0,8 and 1 optional)
Voltage380/400 VAC 3P + N , ± 1% (415 VAC optional)
Frequency50Hz / 60Hz
Frequency ToleranceLine synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Efficiency (at 100% load)%94
Output current crest factor3:1
Overload Protection100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other ProtectionsAdvanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD< 2% (at 100% linear load)
BATTERIES
TypeVRLA AGM / GEL / NiCd
Battery Number2x30 (±30): 60 pieces
Float charging voltage± 405 VDC
Float / End of dischg voltage± 300 VDC
Battery HousingExternal
Battery ambient temp25°C
Protections
Battery ambient temp3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic TestingStandard every 72 hours (adjustable)
GENEL
StandardsEN62040-1, EN62040-2, EN62040-3
User Interface4 satır LCD panel, Mimik led panel, 5 vektör butonlar, buzer
IndicatorsP-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
AdvancedSelf diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
CommunicationRS232 serial port, 4 standard DRY contact alarm relays
InputsEPO input
Genset KitStandard (programmable)
SoſtwareStandard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm LoggingStandard:with time & date 512 events
ProtectionsPower module over-temperature, Overcurrent, Temperature high alarm
Temperature Range0°C - 40°C
Protection classIP20
Relative humidity90% max. (non-condensing)
Altitude< 1000m above sea level
Noise level< 57 dBA
Weight (kg)49.5
Dimension (mm) HxWxD700x300x770 (without batt.) / 1000x300x800 (with 5ah batt.) /1170x300x800 (with 7-9ah batt.)
OPTIONS
Input / Output voltagePlease ask
Comm. adaptorsSNMP, MODBUS, RS485, Remote panel
SoſtwareT-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
TECHNICIAL SPECIFICATIONS
Nominal power (kVA)20
INPUT
Voltage380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional)
Frequency50Hz / 60Hz, ± %10
Power factor (at100% load)≥ 0.99
THDI (at 100% load)≤ 4% (depends on mains input conditions)
By-Pass Voltage380/400 VAC 3 Phase + N, ± 10%
ProtectionFuses, Voltage & Frequency Tolerance
OUTPUT
Power (kW)18
Power factor0,9 (0,8 and 1 optional)
Voltage380/400 VAC 3P + N , ± 1% (415 VAC optional)
Frequency50Hz / 60Hz
Frequency ToleranceLine synchronized: ± 2% (adjustable) / Free running: ± 0,1%
Efficiency (at 100% load)%94
Output current crest factor3:1
Overload Protection100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other ProtectionsAdvanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
THD< 2% (at 100% linear load)
BATTERIES
TypeVRLA AGM / GEL / NiCd
Battery Number2x30 (±30): 60 pieces
Float charging voltage± 405 VDC
Float / End of dischg voltage± 300 VDC
Battery HousingExternal
Battery ambient temp25°C
Protections
Battery ambient temp3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic TestingStandard every 72 hours (adjustable)
GENEL
StandardsEN62040-1, EN62040-2, EN62040-3
User Interface4 satır LCD panel, Mimik led panel, 5 vektör butonlar, buzer
IndicatorsP-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
AdvancedSelf diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
CommunicationRS232 serial port, 4 standard DRY contact alarm relays
InputsEPO input
Genset KitStandard (programmable)
SoſtwareStandard T-Mon UPS Management Soſtware (3 clients + 1 server management)
Alarm LoggingStandard:with time & date 512 events
ProtectionsPower module over-temperature, Overcurrent, Temperature high alarm
Temperature Range0°C - 40°C
Protection classIP20
Relative humidity90% max. (non-condensing)
Altitude< 1000m above sea level
Noise level< 57 dBA
Weight (kg)51
Dimension (mm) HxWxD700x300x770 (without batt.) / 1000x300x800 (with 5ah batt.) /1170x300x800 (with 7-9ah batt.)
OPTIONS
Input / Output voltagePlease ask
Comm. adaptorsSNMP, MODBUS, RS485, Remote panel
SoſtwareT-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients