| TECHNICIAL SPECIFICATIONS |
| Nominal power (kVA) | 20 |
| INPUT |
| Voltage | 380/400 VAC 3P + N + G ± 20% (at 100% load) / - 40% (at 70% load) |
| Frequency | 50Hz / 60Hz, ± 10% |
| Power factor (at100% load) | ≥ 0.99 (at 100% load) |
| THDI (*) | ≤ %3 |
| By-Pass Voltage | 380/400 VAC 3 Phase + N, ± 10% |
| Protection | Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator |
| OUTPUT |
| Power (kW) | 18 |
| Input Voltage regulation | 0,9 (0,8 and 1 optional) |
| Voltage | 380/400 VAC 3P + N, ± 1% (415 VAC optional ) |
| Frequency | 50Hz / 60Hz |
| Frequency Tolerance | Line synchronized: ± 0,1% (adjustable) / Free running: ± 0,02% |
| Efficiency | up to 95% |
| Output current crest factor | 3:1 |
| Overload Protection | 100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass |
| Other Protections | Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting |
| THD | ≤ 2% (at 100% linear load) |
| BATTERIES |
| Type | Bakım gerektirmeyen kuru tip |
| Battery Number | 2x30 (±30) : 60 pieces |
| Float charging voltage | 2x405 VDC |
| Float / End of dischg voltage | 2x300 VDC |
| Battery Housing | Internal |
| Battery ambient temp | 25ºC |
| Protection | 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) |
| Automatic Testing | Standard every 72 hours (adjustable) |
| GENEL |
| Standards | EN62040-1, EN62040-2, EN62040-3 |
| User Interface | 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel |
| Indicators | P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time |
| Advanced | Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter |
| Communication | 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays |
| Inputs | EPO input, Interactive battery panel input, Genset input |
| Soſtware | Standard T-Mon UPS Management Soſtware (3 clients + 1 server management) |
| Alarm Logging | Standard:with time & date 512 events |
| Protections | Power module over-temperature, Overcurrent, Temperature high alarm |
| Temperature Range | 0ºC - 40ºC |
| Protection class | IP20 |
| Relative humidity | 90% max. (non-condensing) |
| Altitude | < 1000m above sea level |
| Noise level | < 57dBA |
| Weight (kg) | 91 |
| Dimension (mm) HxWxD | 400x815x1040 |
| OPTIONS |
| Input / Output voltage | Please ask |
| Transformer | Galvanic isolation transformer at the input & output (internal) |
| Soſtware | T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients |
| Comm. adaptors | SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem, Comport multiplexer |
| Parralel Operation | Up to 8 units |
| NOT |
| (*) | Depending on power and input/output conditions |
| Voltage tolerance | ≤ % ±1 Stabil, ≤ % ±5 Stabil olmayan |
| Genset Kit | Standard (programmable) |