TEOS 300 UPS SERIES

3/3 Uninterruptible Power Supplies

30kVA - 80kVA



• True double-conversion
• DSP technology guarantees high performance
• Output power factor 1.0
• Active power factor correction in all phases
• 50Hz/60Hz frequency converter mode
• ECO mode operation for energy saving
• Emergency power off function (EPO)
• Generator compatible
• ECOMODE
• SNMP+USB+RS-232 multiple communications
• 3-stage extendable charging design for optimized battery performance
• Adjustable battery numbers for long-run model
• Maintenance bypass available
• Parallel operation with commom battery
• Optional parallel operation (up to 3 pcs)
• Optional isolation transformer offers full isolation and complete common mode noise rejection

MODEL
Teos 330 XL
Teos 340 XL
Teos 360 XL
Teos 380 XL
Phase
3 phase in / 3 phase out
Capacity
30kVA / 30kW
40kVA / 40kW
60kVA / 60kW
80kVA / 80kW
Parallel capability
up to 3 units in parallel
INPUT
Nominal voltage
3x400VAC (3Ph+N)
Input voltage range
190-520VAC (3-Phase) @ 50% load  
305-478 VAC (3-phase) @ 100% load
Frequency range
46~54Hz or 56~64Hz
Power factor
≥ 0.99  @ 100% load 
OUTPUT
Voltage
3 x 360/380/400/415 VAC (3Ph+N) 
AC Voltage regulation  (battery mode)
± 1%
Frequency range (synchronized range)
46~54Hz or 56~64Hz
Frequency range (batt. mode)
50Hz ± 0.1Hz or 60Hz ± 0.1Hz (batt. mode)
Current crest ratio
3:1 (max.)
Harmonic distortion
≤ 2 % THD (Linear Load)  ≤ 4 % THD (Non-linear Load)
Transfer time AC Mode to batt. Mode
Zero
  Inverter to bypass
Zero
Waveform (Batt. mode)
Pure sinewave
Overload AC mode
100-110% for 10 min, 110-130% for 1 min, >130% for 1 second
  Battery mode
100-110% for 30 seconds, 110-130% for 10 seconds, >130% for 1 second
EFFICIENCY
AC Mode
95.5%
Eco mode
97%
Battery mode
93.5%
BATTERY
Battery type
Depending on the capacity of external batteries
Numbers
64 pcs 12V 7Ah or 64 pcs 12V 9Ah internal battery
32~40 pcs (adjustable)
Charging current (max.)
1A-12A(adjustable)
2A-12A (adjustable)
Charging voltage
±13.65VxN  (N = 16~20)
INDICATORS
LCD panel
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
PHYSICAL
Dimension, HxWxD (mm)
1000x300x815
1010x360x790
Net Weight (kg)
60
61
108
113
ENVIRONMENT
Operating temperature
0-40°C
Operating humidity
< 95% and non-condersing
Acoustic noise
Less than 60dBA @ 1 Meter
Less than 70dBA @ 1 Meter
Less than 75dBA @ 1 Meter
MANAGEMENT
Smart RS-232/USB
Supports Windows® 2000/2003/XP/Vista/2008, 7/8, Linux and MAC
Optional SNMP
Power management from SNMP manager and web browser